Selection Instructions for Electroplating Chillers
Edit: 管理员  Date: 2017-03-16

How to quickly select electroplating chillers for customers in the electroplating industry? The solutions are as follows
1. The type selection is based on the electroplating tank volume, the number of electroplating tanks, and the concentration of solution in the electroplating tank. The calculation formula is as follows:
Step 1: (electroplating tank volume * 70%) * number of electroplating tanks=flow rate (tons)
Step 2: Flow * Temperature difference * 1.167 * 120%=Cooling capacity
Step 3: Select the type based on the cooling capacity
Note: a. The 70% in the first step of the formula refers to that the electroplating tank will not be filled with solution under normal circumstances, so it is 70% instead of 100%.
B. The second step in the formula, 100% (safety factor), refers to the configuration of a water chiller based on a 20% increase in the cooling capacity of the electroplating tank under normal conditions. The cooling effect can only be achieved if the cooling capacity of the OWADA/Daiwa company equipment is greater than the cooling capacity required by the customer's equipment.
2. Selection based on the current and voltage of the current vibrator
Calculation formula: current of vibrator (A) * voltage of vibrator (V) * 70%=cooling capacity
Selection based on cooling capacity
Note: In the formula, 70% refers to the selection based on 70% of the total power of the vibrator and the cooling capacity of the chiller. This method is relatively good for selection.
3. Selection based on the heating capacity of the vibrator
Heating capacity of the vibrator * (1+(10% - 30%)=cooling capacity
Selection based on cooling capacity
Note: In the formula, 10% - 30% means that the cooling capacity must be greater than 10% - 30% of the calorific value to achieve the cooling effect, and cannot be lower than 10%.
Material Selection for Important Components of Electroplating Chillers in Electroplating Industry
Direct cooling: refers to the customer directly pumping the electroplating solution into a water chiller for cooling. (Select materials based on the concentration of the electroplating solution) When the concentration of the electroplating solution is high, a chemical pump should be used, and titanium tubes should be used in the evaporator.
Indirect cooling: Refers to the configuration of titanium tubes in the electroplating tank by the customer, and the cooling machine passes through the titanium tubes to cool the electroplating solution. It must be noted that the quality of the titanium tubes in the electroplating tank by the customer is very important. Conversely, once the titanium tubes are of poor quality and corroded, the consequences can be unimaginable.
Daheda originated in Taiwan, specializing in industrial refrigeration equipment and industrial temperature control equipment for 12 years; Supplier of heating and cooling design solutions and solutions!
Ohata can provide customers with:
》High performance temperature control unit
》Short lead times and competitive prices
》A one-stop solution from design to manufacturing
》Advanced supporting technology and perfect after-sales service
》Our production base: Dongguan, Taiwan
Main products: industrial water chillers, water cooled water chillers, air cooled water chillers, screw water chillers, water cooled screw water chillers, air cooled screw water chillers, low-temperature water chillers, water cooled low-temperature water chillers, air cooled low-temperature water chillers, water cooled screw low-temperature water chillers, air cooled screw low-temperature water chillers, electroplating water chillers, chemical water chillers, aquaculture dedicated water chillers, open water chillers, vacuum coating water chillers Dongguan water chiller, Shenzhen water chiller, Fujian water chiller, Xiamen water chiller, Suzhou water chiller, Shanghai water chiller, Hubei water chiller, Hunan water chiller, foam water chiller, surface treatment water chiller, injection molding water chiller, PCB water chiller, concrete specific water chiller, food specific water chiller, refrigeration unit, oil cooler, cooling tower, mold temperature machine, plastic dehumidifier, plastic dryer, plastic shredder, plastic mixer Plastic mixer, plastic suction machine, mold rack.